(1)變壓器不能(neng)停運時的(de)臨時排除方法:
①有外引接地(di)線,如果故(gu)障電流較(jiao)大時(shi),可臨時(shi)打開地(di)線運行(xing)。但必須加強監視,以(yi)防故(gu)障點消(xiao)失(shi)后(hou)使(shi)鐵芯出現懸浮電位。
②如果多點接地(di)故(gu)障屬(shu)于不(bu)穩定(ding)型,可在(zai)(zai)工作接地(di)線(xian)中串入一個滑線(xian)電(dian)阻,使電(dian)流限制在(zai)(zai)1A以(yi)下。滑線(xian)電(dian)阻的選擇,是將正常工作接地(di)線(xian)打開測得(de)的電(dian)壓除以(yi)地(di)線(xian)上的電(dian)流。
③要用色譜分析監(jian)視故(gu)障點的產氣速率。
④通過(guo)測量找(zhao)到確(que)切(qie)的故(gu)(gu)障(zhang)點后,如果無法處(chu)理,則可將鐵芯的正(zheng)常工(gong)作接地片移(yi)至故(gu)(gu)障(zhang)點同(tong)一位(wei)置,用以(yi)較大幅度(du)地減少環(huan)流。
(2)徹底檢修措施。監(jian)測發現變壓器(qi)存在多(duo)點(dian)(dian)(dian)(dian)接(jie)(jie)(jie)地故障(zhang)后,對于(yu)可停(ting)運(yun)的變壓器(qi),應(ying)及(ji)時停(ting)運(yun),退出后徹底消除多(duo)點(dian)(dian)(dian)(dian)接(jie)(jie)(jie)地故障(zhang)。排(pai)除此(ci)類故障(zhang)的方法,根據多(duo)點(dian)(dian)(dian)(dian)接(jie)(jie)(jie)地類型及(ji)原(yuan)因(yin),應(ying)采取相應(ying)的檢修措施。但也(ye)有某些情況,停(ting)電吊芯后找不到故障(zhang)點(dian)(dian)(dian)(dian),為了能確切找到接(jie)(jie)(jie)地點(dian)(dian)(dian)(dian),現場可采用如下方法。
①直流法(fa)。將鐵芯和(he)夾件的(de)連(lian)接片打開,在軛兩(liang)側的(de)硅(gui)鋼片上通(tong)入6V的(de)直流,然后用直流電(dian)壓表依次測量各(ge)級硅(gui)鋼片間的(de)電(dian)壓,當電(dian)壓等于(yu)零(ling)或者表指示反向(xiang)時,則(ze)可認(ren)為該處是(shi)故障(zhang)接地點。
②交流法。將變壓器低壓繞組接(jie)入交流電(dian)(dian)壓220~380V,此時鐵芯中有磁通存在。如果有多點接(jie)地故障(zhang)時,用(yong)毫(hao)安(an)表測(ce)量(liang)會出現電(dian)(dian)流(鐵芯和夾件的連(lian)接(jie)片應打開)。用(yong)毫(hao)安(an)表沿鐵軛各級逐點測(ce)量(liang),當毫(hao)安(an)表中電(dian)(dian)流為零時,則該處(chu)為故障(zhang)點。